MCB测试选项,监控电压适配器以测试现场最多250A的MCBS。用DIN导轨安装在顶盖上的测试面板,以测试一次断路断路器。还可在独立的外壳(PTE-FCD)中提供PTE-FCB / PTE-FCD可用于有效降低显示器输入的灵敏度。The monitor input detects the relay’s operation and stops (or starts) the chronometer when testing with the PTE-100-C, PTE-50-CE, PTE-50-CET, and LETs Our timer can be programmed to stop when a significant amount of voltage appears across the MONITOR section. This is the preferred method to measure trip time in a single-pole MCB (miniature circuit breaker), because, being single-pole, there is no associated ‘dry’ contact that can be used to detect the trip operation. You inject the trip current across the MCB and, when it trips, the applied voltage appears across its poles. The PTE-FCD is required because there is also a voltage drop across the closed MCB, and it may be so significant as to activate the monitor, which intempestively stops the chronometer before the MCB has tripped, thus rendering the test impossible. With the PTE-FCD, you can attenuate this ‘non-trip’ voltage until it is no longer detected by the monitor, without affecting the detection of the ‘trip voltage’. Once you have adjusted it for the particular MCB, you can proceed with the testing. The PTE-FCD is actually an integral part of the PTE-FCB optional accessory that installs inside the PTE-100-C’s cover. However its functionality is useful also for other customers who need to test single-pole MCBs or similar tripping devices with test equipment other than the PTE-100-C (e.g. the LETs).