• NAMUR SERIES WITH LED diameter 8 mm • ATEX certified II 1GD for zone 0;20 • Connector output M12 x 1 General features: With this new series of sensors it’s possible to drive specific inputs for NAMUR sensors or inputs for 2 wires amplified switches with low current (up to 10 mA). The load can be applied on both terminals (function PNP or NPN). The output is internally triggered and monitored by LED. Technical data: • Working voltage: 7,7 ÷ 9 Vdc • Max ripple: 10% • Off-state current (Ir ): ≤ 1 mA • Minimum operational current (Im): 2 mA • Rated operational current (Ie): 10 mA • Voltage drop (Ud) with load 10 mA: < 6,5 V • Voltage drop (Ud) with load 8 mA: < 5 V • Temperature range: - 20° ÷ +60°C • Max thermal drift of sensing distance Sr : ± 10% • Repeat accuracy (R): 2% • Switching hysteresis max (H): 10% • Degree of protection: IP67 • Switch status indicator: yellow LED • Marking: II 1D Ex iaD 20 T80°C II 1G Ex ia IIC T6 • Certified IMQ 08 ATEX 011 X • Protected against any wrong connection • Electromagnetic compatibility (EMC) according to EN60947-5-2 • According to: EN60947-5-6/EN60079-0/EN60079-11/EN60079-26 • Shock and vibration resistance according to EN60068-2-27/EN60068-2-6 Safety parameters: • Vi max: 13,5 V • Ii max: 60 mA • Ci max: 100 nF • Li max: 100 μH • Pi max: 200 mW These sensors must be used in conjunction with associated apparatus (See Sect. E) Use in hazardous area according to instruction manuals