1型和2型保护器符合UNE-EN 61643-11和REBT的GUIDEBT- 23。适用于REBT规定的第一类、第二类、第三类、第四类设备。>内部气体放电管。>为了方便布线而进行双连接(限制为63 A)。>可以连接到M5叉形终端。>用于TT系统。>与ATSUB、ATCOVER等其他spd协调。>快速反应。>能耐100kA直击雷击电流(10/350μs波)。>限制电流以下的供电。带有发光报警的热力控制装置。 > It has a test button to check the status of the protector. If the warning light illuminates in protective green in good condition. If not replace. > This indicator does not generate any operating current resulting from state control and does not increase leakage to ground during normal operation ATSHOCK series protectors have been tested in offi cial, independent laboratories obtaining their characteristics according to applicable standards (shown in the table). INSTALLATION ATSHOCK T25 surge protection devices are to be installed in parallel with the low voltage supply line, connected to a phase, neutral and ground. The power should be disconnected during the installation of the SPD. It can be installed in combination with ATSUB or ATCOVER. In either case, both must be separated by at least 10 meter cable or, if this is not possible, by a decoupling inductor ATLINK, in order to achieve a correct coordination between them. Classifi ed by IBERDROLA as protection against transient overvoltages Type 1 in Electricity Meter Room.